1 process data object identifiers, Process data object identifiers – Lenze E94ARNE Regenerative power supply User Manual
Page 112
9400 regenerative power supply module | Parameter setting
"CAN on board" system bus
Process data transfer
112
L
EDS94ARNExxxx EN 2.3 - 06/2014
6.6.1
Process data object identifiers
In the Lenze setting, the identifier for the process data objects PDO1 ... PDO4 consists of a
basic identifier and the node address set in
:
Identifier (COB-ID) = basic identifier + node address (node ID)
In the Lenze setting, the basic identifiers of the PDOs are preset according to the
"Predefined Connection Set" of DS301 V4.02.
The PDO identifier settings can be changed via the Lenze codes and CANopen indexes
listed in the following table. In this way, you can also set an identifier independent of
the node address for certain PDOs.
Tip!
The "Predefined Connection Set" can always be restored via the following device
commands (
• "93: CAN on-board: Pred.Connect.Set" for on-board CAN
• "94: CAN module: Pred.Connect.Set" for communication module E94AYCCA
Process data object
Basic identifier
Individual setting
dec
hex
Lenze code
CANopen index
PDO1
RPDO1
512
0x200
TPDO1
384
0x180
PDO2
RPDO2
768
0x300
TPDO2
640
0x280
PDO3
RPDO3
1024
0x400
TPDO3
896
0x380
PDO4
RPDO4
1280
0x500
TPDO4
1152
0x480
Note!
When the node address has been changed (
) and CAN reset node is
executed subsequently, the subcodes of
are automatically
set to the identifiers resulting from the respective basic identifier and the node
address set.