Via the, I-1029, I-1018 – Lenze E94ARNE Regenerative power supply User Manual
Page 155

EDS94ARNExxxx EN 2.3 - 06/2014
L
155
9400 regenerative power supply module | Parameter setting
"CAN on board" system bus
Implemented CANopen objects
I-1018
I-1029
This object serves to set the communication state to which the regenerative power supply
module will change after a bus off, node/life guarding event or heartbeat event.
Index:
I-1018
Name:
Identity object
Subindex
Default setting
Display range (min. value | unit | max. value)
Access
Data type
0: Highest subindex supported
See below
0
4294967295 ro
U32
1: Vendor-ID
2: Product code
3: Revision number
4: Serial number
Subindex
Meaning
1
Vendor identification number
• The identification number assigned to Lenze by the "CAN in Automation e. V."
organisation is "0x0000003B".
2
Product code
0x94001 9400 StateLine
0x94002 9400 HighLine
0x94004 9400 regenerative power supply module
3
Main version and subversion of the firmware
4
Serial number
Index:
I-1029
Name:
Error behaviour
Subindex
Default setting
Setting range (min. value | unit | max. value)
Access
Data type
0: Highest subindex supported
1
- (read access only)
ro
U8
1: Communication error
0
0
2 rw
U8
Subindex
Meaning
Lenze code
1
State change after bus off, node/life guarding event or
heartbeat event:
0 State change from "operational" to "pre-
operational"
1 No state change
2 State change to "stopped"