EDS94ARNExxxx EN 2.3 - 06/2014
L
125
9400 regenerative power supply module | Parameter setting
"CAN on board" system bus
Parameter data transfer
6.7.2.3
Data 1 ... data 4
A maximum of 4 bytes is available for parameter value entries. Depending on the data
format, these bytes are assigned as follows:
Example
The value "123.45" is to be transferred for a code with the scaling factor "100" and the data
format U32.
Calculation:
Value to be transferred = scaling factor x value
Data
(1 ... 4)
= 100 x 123.45 = 12345 (0x00 00 30 39)
Entries:
1st byte
2nd byte 3rd byte
4th byte
5th byte
6th byte
7th byte
8th byte
Command
Index
Subindex
Data 1
Data 2
Data 3
Data 4
Low byte High byte
Low word
High word
Low byte
High byte
Low byte
High byte
5th byte
6th byte
7th byte
8th byte
Parameter value (1 byte)
0x00
0x00
0x00
Parameter value (2 bytes)
0x00
0x00
Low byte
High byte
Parameter value (4 bytes)
Low word
High word
Low byte
High byte
Low byte
High byte
Note!
For all Lenze parameters a scaling factor is specified in the "Factor" column of the
. The scaling factor is important for the transfer of parameter
values which are displayed with one or more decimal places in the parameter
list.
For a scaling factor > 1, the value must be multiplied by the specified scaling
factor before being transferred in order to transfer the value completely (as an
integer). On the SDO client side, the integer then must be divided by the scaling
factor to receive the original value with decimal places.
1st byte
2nd byte 3rd byte
4th byte
5th byte
6th byte
7th byte
8th byte
Command
Index
Subindex
Data 1
Data 2
Data 3
Data 4
0x39
0x30
0x00
0x00