9400 regenerative power supply module | Parameter setting
Device interface
Device commands
40
L
EDS94ARNExxxx EN 2.3 - 06/2014
4.1.2
Load start parameters
The
= "1: Load start parameters" device command can be used to reload the start
parameters of the active application from the memory module into the regenerative
power supply module:
[4-2]
"Load start parameters" function
Only possible when the controller is inhibited and the application has been stopped.
All parameter changes made since the last saving of the parameter set will get lost!
This device command only has an impact on the settings of the operating system,
application, and module parameters, the active application remains unchanged.
Possible status displays for this device command
Related device commands
* In this example application 1 is the active application
PS
9400
RAM
Firmware
Application 1*
PS
Application 3
PS
Application 2
PS
Memory module MM
PS
Application 1*
Status (
Meaning
99586 Device command in process
65536 Device command executed successfully
65537 General fault
99371 Fault while reading the parameter set partition
99374 No memory module available
104960 CAN fault
... ...
105215 CAN fault