3 masking of tpdos for event control, 4 data reception monitoring of rpdos, Masking of tpdos for event control – Lenze E94ARNE Regenerative power supply User Manual
Page 114: Data reception monitoring of rpdos

9400 regenerative power supply module | Parameter setting
"CAN on board" system bus
Process data transfer
114
L
EDS94ARNExxxx EN 2.3 - 06/2014
6.6.3
Masking of TPDOs for event control
For TPDO1 ... TPDO4, a mask can be parameterised for each byte. If event-controlled
transmission is selected for a PDO, only the masked bits are evaluated.
Mask "0x0" means that no bit of the corresponding byte activates PDO transmission.
Mask "0xff" means that each bit of the corresponding byte can activate PDO
transmission.
Short overview: parameters for masking the TPDOs
6.6.4
Data reception monitoring of RPDOs
For each of the RPDOs 1 ... 4 a monitoring time can be set, within which the RPDO must
arrive. If the RPDO is not received within the monitoring time or with the configured sync,
the response parameterised for the respective RPDO is triggered.
Short overview: parameters for RPDO monitoring
Parameter
Information
Lenze setting
CAN TPDO1 mask byte x
0x00
CAN TPDO2 mask byte x
0x00
CAN TPDO3 mask byte x
0x00
CAN TPDO4 mask byte x
0x00
Parameter
Information
Lenze setting
Value Unit
CAN RPDOx monitoring time
3000 ms
Resp. to CAN-RPDOx error
No response