beautypg.com

Can module (mxi1): lifeguarding error [0x009e0020, 0x009d0002, 0x009e0000 – Lenze E94ARNE Regenerative power supply User Manual

Page 245: 0x009d0001, 0x009e0020, Diagnostics & fault analysis error messages

background image

EDS94ARNExxxx EN 2.3 - 06/2014

L

245

9400 regenerative power supply module | Parameter setting

Diagnostics & fault analysis

Error messages

CAN module (MXI1): Invalid node address 0 [0x009d0001]

CAN module (MXI1): Basic configuration invalid [0x009d0002]

CAN module (MXI1): Heartbeat error index 1 ... 32 [0x009e0000 ... 0x009e001f]

CAN module (MXI1): Lifeguarding error [0x009e0020]

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

CANopen communication module in MXI1: Initialisation

error

• The hardware assignment of the node address has

been selected via DIP switch and the DIP switches for

the node address are set to zero.

• Note: Instead of the impermissible node address 0 the

node address 1 is used.

• Set the DIP switches to a node address unequal 0 and

restart the controller.

• Activate the node address assignment by means of

software by changing the position of DIP switch 2 and

restart the controller.

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

CANopen communication module in MXI1:

Configuration error

• Faulty download of an Engineer or PLC Designer

project

• Invalid CAN settings according to DS301V402 in the

Engineer or PLC Designer.

• Repeat download

• Correct CAN settings in the project and regenerate

project.

Response (Lenze setting printed in bold)

Setting:

C13613/1...32

( adjustable response)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

CANopen communication module in MXI1: Cyclic node

monitoring

• Node has not received a heartbeat telegram from

node 1 ... 32 within the defined time.

• Reactivate CAN node by mains switching, restart of

the regenerative power supply module,

(

C00002

="11000") or CAN reset node.

• Reparameterise the heartbeat producer monitoring

time or switch off monitoring and reset locked error

status, if necessary.

Tip: Save the current parameter set before mains

switching and restarting the regenerative power supply

module (

C00

002

="11").

Response (Lenze setting printed in bold)

Setting:

C13614

( Adjustable response)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

CANopen communication module in MXI1: Cyclic node

monitoring

• Slave response: Maximum time between two node

guarding telegrams (remote transmission request

telegram) from the master has been exceeded.

Reparameterise the life guarding monitoring time or

switch off monitoring.