Power section is defect [0x00680001, Memory module is defect or missing [0x00680002, Safety module is defect or missing [0x00680003 – Lenze E94ARNE Regenerative power supply User Manual
Page 210: Mxi1: module changed during operation [0x00680004, Mxi2: module changed during operation [0x00680005, 0x00680002, 0x00680004, 0x00680005, 0x00680001, 0x00680003
9400 regenerative power supply module | Parameter setting
Diagnostics & fault analysis
Error messages
210
L
EDS94ARNExxxx EN 2.3 - 06/2014
Power section is defect [0x00680001]
Memory module is defect or missing [0x00680002]
Safety module is defect or missing [0x00680003]
MXI1: Module changed during operation [0x00680004]
MXI2: Module changed during operation [0x00680005]
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
Operating system could not identify the power section. Mains switching
• Please contact Lenze if the error occurs again.
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
Operating system could not identify the memory
module.
Mains switching
• If the error occurs again: switch off regenerative
power supply module, unplug memory module and
plug it in again, switch on regenerative power supply
module again.
• If the error still occurs: switch off regenerative power
supply module and use a different memory module.
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
Operating system could not identify the safety module. Mains switching
• If the error occurs again: switch off regenerative
power supply module, unplug safety module and plug
it in again, switch on regenerative power supply
module again.
• If the error still occurs: switch off regenerative power
supply module and use a different safety module.
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
The extension module you have tried to plug into the
module slot MXI1 is not "hot plug" capable.
Plug in suitable module and switch mains.
• Through mains switching, the system accepts
modules without "hot plug" capability in the
following switch-on phase.
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
The extension module you have tried to plug into the
module slot MXI2 is not "hot plug" capable.
Plug in suitable module and switch mains.
• Through mains switching, the system accepts
modules without "hot plug" capability in the
following switch-on phase.