Can on board: bus-off [0x00830000, Can on board: invalid node address 0 [0x00830001, 0x00830002 – Lenze E94ARNE Regenerative power supply User Manual
Page 232: 0x00830000, 0x00830001, 0x007f0004, Diagnostics & fault analysis error messages
9400 regenerative power supply module | Parameter setting
Diagnostics & fault analysis
Error messages
232
L
EDS94ARNExxxx EN 2.3 - 06/2014
Communication with module in MXI2 interrupted [0x007f0004]
CAN on board: bus-off [0x00830000]
CAN on board: Invalid node address 0 [0x00830001]
CAN on board: Basic configuration invalid [0x00830002]
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
It is not possible to establish communication between
the regenerative power supply module and the
extension module in the MXI2 module slot.
• Switch off regenerative power supply module, insert
extension module correctly in module slot MXI2, and
switch on the regenerative power supply module
again.
• If the problem occurs again, replace the extension
module.
Response (Lenze setting printed in bold)
Setting:
( Adjustable response)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
CAN on board: "Bus off" state
• Too many faulty telegrams received.
• Defective cable (e.g. loose contact).
• Two nodes with the same ID.
• Eliminate disturbances (e.g. EMC).
• Remove loose contact, screw down adapter.
• Assign different node IDs.
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
CAN on board: initialisation error
• The hardware assignment of the node address has
been selected via DIP switch and the DIP switches for
the node address are set to zero.
• Note: Instead of the impermissible node address 0 the
node address 1 is used.
• Set the DIP switches to a node address unequal 0 and
restart the controller.
• Activate the node address assignment by means of
software by changing the position of DIP switch 2 and
restart the controller.
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
CAN on board: configuration error
• Faulty download of an Engineer or PLC Designer
project
• Invalid CAN settings according to DS301V402 in the
Engineer or PLC Designer.
• Repeat download
• Correct CAN settings in the project and regenerate
project.