9400 regenerative power supply module | Parameter setting

Parameter reference

Parameter list | C00571

314

L

EDS94ARNExxxx EN 2.3 - 06/2014

C00571

C00572

C00573

C00574

Parameter | Name:

C00571 | Resp. brake resist. i2t > C00572

Data type: UNSIGNED_32

Index: 24004

d

= 5DC4

h

Response to be initiated when adjustable warning threshold (

C00572

) of brake resistor monitoring is reached.

Parameterising the brake chopper/brake resistor

Selection list

(Lenze setting printed in bold)

1 Fault
2 Trouble

12 Trouble: chopper off

5 Warning
4 Warning locked
0 No response

Read access  Write access  CINH  PLC STOP  No transfer

Parameter | Name:

C00572 | Warning thres. brake resistor

Data type: UNSIGNED_32

Index: 24003

d

= 5DC3

h

Warning threshold for brake resistor monitoring

• The response to be initiated when the threshold is reached can be selected in

C00571

.

Parameterising the brake chopper/brake resistor

Setting range

(min. value | unit | max. value)

Lenze setting

0

%

100 90 %

Read access  Write access  CINH  PLC STOP  No transfer

Parameter | Name:

C00573 | Resp. to overload brake trans.

Data type: UNSIGNED_32

Index: 24002

d

= 5DC2

h

Response triggered by brake chopper monitoring

Parameterising the brake chopper/brake resistor

Selection list

(Lenze setting printed in bold)

1 Fault
2 Trouble
5 Warning
4 Warning locked
0 No response

Read access  Write access  CINH  PLC STOP  No transfer

Parameter | Name:

C00574 | Resp. to overtemp. brake resist.

Data type: UNSIGNED_32

Index: 24001

d

= 5DC1

h

Response triggered by brake resistor monitoring

Parameterising the brake chopper/brake resistor

Selection list

(Lenze setting printed in bold)

1 Fault
2 Trouble

12 Trouble: chopper off

5 Warning
4 Warning locked
0 No response

Read access  Write access  CINH  PLC STOP  No transfer