C00173 | mains voltage, C00175 | service code, C00176 | service code – Lenze E94ARNE Regenerative power supply User Manual
Page 287: C00177 | service code, C00178 | elapsed hour meter, C00179 | power-on time meter, Lenze setting in, C00173, Setting in, Displa

EDS94ARNExxxx EN 2.3 - 06/2014
L
287
9400 regenerative power supply module | Parameter setting
Parameter reference
Parameter list | C00173
C00173
C00175
C00176
C00177
C00178
C00179
Parameter | Name:
C00173 | Mains voltage
Data type: UNSIGNED_8
Index: 24402
d
= 5F52
h
Adaptation of the DC bus voltage thresholds
• Check during commissioning and adapt, if necessary.
• All drive components connected to the DC bus must have the same thresholds.
• For selection 0 ... 3, the undervoltage threshold is firmly defined depending on the device type (see "Rated data"
chapter in the Hardware Manual).
Note: Altering this setting also has an impact on the permissible device utilisation!
In the chapter "Rated data" of the Hardware Manual, the device types and their permissible utilisation at different
mains voltages and switching frequencies are specified.
Selection list
(Lenze setting printed in bold)
Information
0 230 V
Operation on 230 V mains
• Undervoltage threshold is firmly defined.
• Overvoltage threshold = 400 V
• Brake chopper threshold = 390 V
1 400/415 V
Operation on 400 V mains/415 V mains
• Undervoltage threshold is firmly defined.
• Overvoltage threshold = 800 V
• Brake chopper threshold = 725 V
2 460/480 V
Operation on 460 V mains/480 V mains
• Undervoltage threshold is firmly defined.
• Overvoltage threshold = 800 V
• Brake chopper threshold = 765 V
3 500 V
Operation on 500 V mains
• Undervoltage threshold is firmly defined.
• Overvoltage threshold = 800 V
• Brake chopper threshold = 790 V
Read access Write access CINH PLC STOP No transfer
Parameter | Name:
C00175 | Service code
Data type: UNSIGNED_32
Index: 24400
d
= 5F50
h
This code is used internally by the device and must not be overwritten by the user!
Parameter | Name:
C00176 | Service code
Data type: UNSIGNED_32
Index: 24399
d
= 5F4F
h
This code is used internally by the device and must not be overwritten by the user!
Parameter | Name:
C00177 | Service code
Data type: UNSIGNED_32
Index: 24398
d
= 5F4E
h
This code is used internally by the device and must not be overwritten by the user!
Parameter | Name:
C00178 | Elapsed hour meter
Data type: UNSIGNED_32
Index: 24397
d
= 5F4D
h
Display range
(min. value | unit | max. value)
0
s
4294967295
Read access Write access CINH PLC STOP No transfer
Parameter | Name:
C00179 | Power-on time meter
Data type: UNSIGNED_32
Index: 24396
d
= 5F4C
h
Display range
(min. value | unit | max. value)
0
s
4294967295
Read access Write access CINH PLC STOP No transfer