9400 regenerative power supply module | Parameter setting

Internal interfaces

LS_LineInterface - line interface

262

L

EDS94ARNExxxx EN 2.3 - 06/2014

LI_bFilterOverloadWarnung

BOOL

Status signal "Filter overload"

TRUE Monitoring for filter overload protection has responded:

• Temperature > 155 °C and

C00583

≠ "no response"

- or -

• temperature >

C00121

and

C00584

≠ "no response"

- or -

• open circuit sensor and

C00594

≠ "no response"

LI_bMainsVoltageOK

BOOL

Status signal "Voltage supply at L1, L2, and L3 OK"

TRUE The required voltage is available at all three mains voltage inputs L1,

L2, and L3.

LI_bOperational

BOOL

Status signal "Regenerative power supply module is ready for regenerative

feedback"

From software version V2.x onwards, the following applies:

TRUE The regenerative power supply module is ready for regenerative

feedback.

• The device is enabled, i.e. no fault or trouble has occurred (pulse

inhibit is not set).

FALSE The regenerative power supply module is not ready for regenerative

feedback because pulse inhibit is set in the device.

For software version V1.x, the following applies:

This signal is not connected with the state of the device state machine and can

therefore be used for automatic error acknowledgement.

TRUE The regenerative power supply module is ready for regenerative

feedback.

The following conditions are met simultaneously:

• Mains voltage is applied.

• Charging of DC bus is completed.

• There is no short circuit or earth fault.

• There is no device overload, i.e. the device utilisation (

C00064

) is

below the warning threshold set in

C00123

.

TRUEFALSE The regenerative power supply module is not ready for regenerative

feedback anymore because one of the conditions listed under "TRUE"

is no longer met.

Conditions for returning to the "ready for regenerative feedback"

state:

• If a mains failure has been detected, the mains voltage has to be

applied for at least two complete periods after mains recovery,

before the LI_bOperational signal is reset to TRUE.

• If a short circuit or earth fault has occurred, the device is ready for

operation again after approx. 2 s, i.e. after this time the

LI_bOperational signal is automatically reset to TRUE.

• The device utilisation evaluation has a hysteresis of 5 %. This

means that the device utilisation (

C00064

) must drop to

< (

C00123

- 5 %) before the LI_bOperational signal is reset to

TRUE.

LI_bLimitationActive

BOOL

Status signal "Limitation active"

TRUE A limitation is active.

LI_bRegenActive

BOOL

Status signal "Regenerative feedback active"

TRUE Regenerative feedback operation is active.

LI_bChopperIsActive

BOOL

Status signal "Brake chopper active"

TRUE The brake chopper is active.

Identifier

Data type

Value/meaning