I-1800/1, I-1800 – Lenze E94ARNE Regenerative power supply User Manual
Page 165

EDS94ARNExxxx EN 2.3 - 06/2014
L
165
9400 regenerative power supply module | Parameter setting
"CAN on board" system bus
Implemented CANopen objects
I-1800
Communication parameter for the transmission of process data via TPDO1
[6-17] Assignment of the data telegram
Procedure for changing the identifier:
1. Deactivate the identifier (set bit 31 to "1").
2. Change the identifier.
3. Activate the identifier (set bit 31 to "0").
Index:
I-1800
Name:
TPDO1 communication parameter
Subindex
Default setting
Setting range (min. value | unit | max. value)
Access
Data type
0: Highest subindex supported
5
- (read access only)
ro
U8
1: COB-ID used by TPDO
0x180 + node ID
0
4294967295 rw
U32
2: Transmission type
254
0
255 rw
U8
3: Inhibit time
0 ms
0
0.1 ms
65535 rw
U16
4: Reserved
-
- (reserved, read or write access results in the error
message 0x06090011)
rw
U8
5: Event timer
0 ms
0
ms
65535 rw
U16
Subindex
Meaning
Lenze code
1
Identifier TPDO1
• The basic setting corresponds to the "Predefined
Connection Set": identifier = 0x180 + node ID
2
TPDO transmission type according to DS301 V4.02
3
Minimum time interval between the transmission of
two identical TPDOs (see DS301 V4.02).
5
Cycle time for the transmission of PDOs with
transmission type "254".
8th byte
7th byte
6th byte
5th byte
Data 4
Data 3
Data 2
Data 1
Bit 31
Bit 30
Bit 29 ... bit 11
Bit 10 ... bit 0
0/1
0/1
Extended identifier*
11-bit identifier
* The extended identifier is not supported - bits 11 ... 29 must be set to "0".
Bit
Setting
Bit 30
0 RTR to this PDO possible (Lenze).
1 RTR to this PDO not possible (cannot be set).
Bit 31
0 PDO is active.
1 PDO is not active.