9400 regenerative power supply module | Parameter setting
Parameter reference
Parameter list | C00878
324
L
EDS94ARNExxxx EN 2.3 - 06/2014
C00878
C01120
C01121
Parameter | Name:
C00878 | Status DCTRL control input
Data type: UNSIGNED_8
Index: 23697
d
= 5C91
h
Display range
(min. value | unit | max. value)
0
1
Subcodes
Information
C00878/1
States of control inputs
C00878/...
C00878/5
Read access Write access CINH PLC STOP No transfer
Parameter | Name:
C01120 | Sync source
Data type: UNSIGNED_8
Index: 23455
d
= 5B9F
h
Selection of the source for the synchronisation signals.
• Only one source at a time can synchronise the drive.
"CAN on board" system bus: sync telegram
Selection list
(Lenze setting printed in bold)
0 OFF
1 CAN on-board
2 CAN module
4 Module in MXI1
5 Module in MXI2
6 Digital input 1
7 Digital input 2
8 Digital input 3
9 Digital input 4
10 Digital input 5
11 Digital input 6
12 Digital input 7
13 Digital input 8
Read access Write access CINH PLC STOP No transfer
Parameter | Name:
C01121 | SYNC cycle time
Data type: UNSIGNED_32
Index: 23454
d
= 5B9E
h
Time with which the phase-locking loop (PLL) in the regenerative power supply module awaits the synchronisation
signals.
• The time set must be compatible to the cycle of the respective synchronisation source.
Note: In case that the synchronisation is carried out via the system bus (CANopen), only integer multiples of 1000 μs
make sense for the setting.
Example: For the system bus the interval between two synchronisation signals has been set with 2 ms. If the system
bus is to be used as synchronisation source, a synchronisation cycle of 2000 μs has to be set in C01121.
"CAN on board" system bus: sync telegram
Setting range
(min. value | unit | max. value)
Lenze setting
250
μs
20000 1000 μs
Read access Write access CINH PLC STOP No transfer