C02732 | analog inputs: dead band, C02733 | analog outputs: gain, C02734 | analog outputs: offset – Lenze E94ARNE Regenerative power supply User Manual
Page 335: C02750 | li_dnactualdcbusvoltage, C02751 | li_dnactuallinecurrent, C02732/1, C02732/2, C02733/1, C02733/2, C02734/1

EDS94ARNExxxx EN 2.3 - 06/2014
L
335
9400 regenerative power supply module | Parameter setting
Parameter reference
Parameter list | C02732
C02732
C02733
C02734
C02750
C02751
Parameter | Name:
C02732 | Analog inputs: Dead band
Data type: INTEGER_32
Index: 21843
d
= 5553
h
Setting range
(min. value | unit | max. value)
0.00
%
100.00
Subcodes
Lenze setting
Information
C02732/1
0.00 %
Analog input 1: Dead band
C02732/2
0.00 %
Analog input 2: Dead band
Read access Write access CINH PLC STOP No transfer
Scaling factor: 100
Parameter | Name:
C02733 | Analog outputs: Gain
Data type: INTEGER_32
Index: 21842
d
= 5552
h
Setting range
(min. value | unit | max. value)
-200.00
%
200.00
Subcodes
Lenze setting
Information
C02733/1
100.00 %
Analog output 1: Gain
C02733/2
100.00 %
Analog output 2: Gain
Read access Write access CINH PLC STOP No transfer
Scaling factor: 100
Parameter | Name:
C02734 | Analog outputs: Offset
Data type: INTEGER_32
Index: 21841
d
= 5551
h
Setting range
(min. value | unit | max. value)
-200.00
%
200.00
Subcodes
Lenze setting
Information
C02734/1
0.00 %
Analog output 1: Offset
C02734/2
0.00 %
Analog output 2: Offset
Read access Write access CINH PLC STOP No transfer
Scaling factor: 100
Parameter | Name:
C02750 | LI_dnActualDCBusVoltage
Data type: INTEGER_32
Index: 21825
d
= 5541
h
From software version V2.0 onwards
Current DC-bus voltage in [%]
• 100 % ≡ 1000 V
Display range
(min. value | unit | max. value)
0.00
%
200.00
Read access Write access CINH PLC STOP No transfer
Scaling factor: 100
Parameter | Name:
C02751 | LI_dnActualLineCurrent
Data type: INTEGER_32
Index: 21824
d
= 5540
h
From software version V2.0 onwards
Current mains current in [%]
• 100 % ≡ I
max_device
(
)
Display range
(min. value | unit | max. value)
0.00
%
200.00
Read access Write access CINH PLC STOP No transfer
Scaling factor: 100