New applications loaded [0x006a0003, Applicationtask: overflow [0x006a0004, Usertask: overflow [0x006a0005 – Lenze E94ARNE Regenerative power supply User Manual
Page 218: Idletask: overflow [0x006a0006, 0x006a0004, 0x006a0002, 0x006a0006, 0x006a0003, 0x006a0005, Diagnostics & fault analysis error messages
9400 regenerative power supply module | Parameter setting
Diagnostics & fault analysis
Error messages
218
L
EDS94ARNExxxx EN 2.3 - 06/2014
Error during the update of inputs and outputs [0x006a0002]
New applications loaded [0x006a0003]
ApplicationTask: Overflow [0x006a0004]
UserTask: Overflow [0x006a0005]
IdleTask: Overflow [0x006a0006]
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
Internal error
Mains switching. Transfer application to the
regenerative power supply module again.
• Please contact Lenze if the problem occurs again.
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
Application has been changed by transmission from the
engineer or loading from the memory module.
- (Information only)
Response (Lenze setting printed in bold)
Setting:
( Adjustable response)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
Program runtime for application task is too long.
Reduce program runtime by:
• Omitting functions (e.g. by reducing the number of
active FBs).
• Optimising functions with respect to the calculating
time.
Response (Lenze setting printed in bold)
Setting:
( Adjustable response)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
Program runtime for user task is too long.
Reduce program runtime by:
• Omitting functions (e.g. by reducing the number of
active FBs).
• Optimising functions with respect to the calculating
time.
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
Program runtime for idle task is too long.
Reduce program runtime by:
• Omitting functions (e.g. by reducing the number of
active FBs).
• Optimising functions with respect to the calculating
time.