95
9400 regenerative power supply module | Parameter setting
I/O terminals
Digital outputs
5.5
Digital outputs
The regenerative power supply module is equipped with 4 freely configurable digital
outputs.
5.5.1
Terminal assignment/electrical data
5.5.2
Parameter setting
Short overview of parameters for the digital outputs:
Note!
Initialisation behaviour:
• After mains switching until the start of the application, the digital outputs
remain set to FALSE.
Exception handling:
• In the case of a critical exception within the application (e.g. reset), the digital
outputs are set to FALSE, taking the terminal polarity parameterised in
into consideration.
Terminal
Use
Electrical data
X4/DO1
...
X4/DO4
Digital output 1 ... 4
LOW level: 0 ... +5 V
HIGH level: +15 ... +30 V
Output current: max. 50 mA per output (external
resistance > 480 Ω at 24 V)
Conversion rate: 1 kHz
X4/24O
External 24 V voltage supply for the digital outputs
X4/GO
Reference potential (digital ground)
GO
24O
DO1
DO2
DO3
DO4
X4
Parameter
Information
Dig. output x: Terminal polarity
Status: Digital outputs
Status word: Digital outputs
Highlighted in grey = display parameter