9400 regenerative power supply module | Parameter setting

I/O terminals

Digital outputs

5.5

Digital outputs

The regenerative power supply module is equipped with 4 freely configurable digital

outputs.

5.5.1

Terminal assignment/electrical data

5.5.2

Parameter setting

Short overview of parameters for the digital outputs:

Note!

Initialisation behaviour:
• After mains switching until the start of the application, the digital outputs

remain set to FALSE.

Exception handling:
• In the case of a critical exception within the application (e.g. reset), the digital

outputs are set to FALSE, taking the terminal polarity parameterised in

C00118

into consideration.

Terminal

Use

Electrical data

X4/DO1

...

X4/DO4

Digital output 1 ... 4

LOW level: 0 ... +5 V

HIGH level: +15 ... +30 V

Output current: max. 50 mA per output (external

resistance > 480 Ω at 24 V)

Conversion rate: 1 kHz

X4/24O

External 24 V voltage supply for the digital outputs

X4/GO

Reference potential (digital ground)

GO

24O

DO1

DO2

DO3

DO4

X4

Parameter

Information

C00118

Dig. output x: Terminal polarity

C00444

Status: Digital outputs

C02802

Status word: Digital outputs

Highlighted in grey = display parameter