0x00b00001, 0x00b00002, 0x00b00003 – Lenze E94ARNE Regenerative power supply User Manual
Page 252: 0x00b00004, 0x00b00005, Diagnostics & fault analysis error messages

9400 regenerative power supply module | Parameter setting
Diagnostics & fault analysis
Error messages
252
L
EDS94ARNExxxx EN 2.3 - 06/2014
CAN module (MXI2) RPDO2: Telegram not received or faulty [0x00b00001]
CAN module (MXI2) RPDO3: Telegram not received or faulty [0x00b00002]
CAN module (MXI2) RPDO4: Telegram not received or faulty [0x00b00003]
CAN module (MXI2) RPDO5: Telegram not received or faulty [0x00b00004]
CAN module (MXI2) RPDO6: Telegram not received or faulty [0x00b00005]
Response (Lenze setting printed in bold)
Setting:
C14591/2
( Adjustable response)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
CANopen communication module in MXI2: CAN-IN 2
error
• Incorrect PDO telegram length.
• Transmission error.
• PDO time monitoring has responded.
• Set the correct telegram length for the CAN master
(sender).
• Eliminate disturbances in the environment (e.g. EMC).
• Select a different monitoring time or switch off time
monitoring.
Response (Lenze setting printed in bold)
Setting:
C14591/3
( Adjustable response)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
CANopen communication module in MXI2: CAN-IN 3
error
• Incorrect PDO telegram length.
• Transmission error.
• PDO time monitoring has responded.
• Set the correct telegram length for the CAN master
(sender).
• Eliminate disturbances in the environment (e.g. EMC).
• Select a different monitoring time or switch off time
monitoring.
Response (Lenze setting printed in bold)
Setting:
C14591/4
( Adjustable response)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
CANopen communication module in MXI2: CAN-IN 4
error
• Incorrect PDO telegram length.
• Transmission error.
• PDO time monitoring has responded.
• Set the correct telegram length for the CAN master
(sender).
• Eliminate disturbances in the environment (e.g. EMC).
• Select a different monitoring time or switch off time
monitoring.
Response (Lenze setting printed in bold)
Setting:
C14591/5
( Adjustable response)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
CANopen communication module in MXI2: CAN-IN 5
error
• Incorrect PDO telegram length.
• Transmission error.
• PDO time monitoring has responded.
• Set the correct telegram length for the CAN master
(sender).
• Eliminate disturbances in the environment (e.g. EMC).
• Select a different monitoring time or switch off time
monitoring.
Response (Lenze setting printed in bold)
Setting:
C14591/6
( Adjustable response)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
CANopen communication module in MXI2: CAN-IN 6
error
• Incorrect PDO telegram length.
• Transmission error.
• PDO time monitoring has responded.
• Set the correct telegram length for the CAN master
(sender).
• Eliminate disturbances in the environment (e.g. EMC).
• Select a different monitoring time or switch off time
monitoring.