beautypg.com

0x00870000, 0x00870001, 0x00860020 – Lenze E94ARNE Regenerative power supply User Manual

Page 234: 0x00860000, Diagnostics & fault analysis error messages

background image

9400 regenerative power supply module | Parameter setting

Diagnostics & fault analysis

Error messages

234

L

EDS94ARNExxxx EN 2.3 - 06/2014

CAN on board: Node guarding error 1 ... 32 [0x00860000 ... 0x0086001f]

CAN on board: Faulty NMT master configuration [0x00860020]

CAN on board RPDO1: Telegram not received or faulty [0x00870000]

CAN on board RPDO2: Telegram not received or faulty [0x00870001]

Response (Lenze setting printed in bold)

Setting:

C00612/1...32

( adjustable response)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

CAN on board: Cyclic node monitoring

• CAN master has not received a response to a node

guarding telegram (remote transmission request

telegram) from node 1 ... 32 within the defined time.

• Reactivate CAN node by mains switching, restart of

the regenerative power supply module,

(

C00002

="11000") or CAN reset node.

• Reparameterise the node guarding monitoring time

or switch off monitoring.

• Reset locked error status if necessary.

Tip: Save the current parameter set before mains

switching and restarting the regenerative power supply

module (

C00

002

="11").

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

CAN on board: A configuration error has occurred in the

network management of the CAN master.

• Faulty download of an Engineer or PLC Designer

project.

• Invalid CAN master settings according to DS301V402

and DS405 in the Engineer or PLC Designer.

• Incorrect parameterisation of node guarding or

heartbeat.

• Repeat download

• Correct CAN settings in the project and regenerate

project.

Response (Lenze setting printed in bold)

Setting:

C00591/1

( Adjustable response)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

CAN on board: CAN-IN 1 error

• Incorrect PDO telegram length.

• Transmission error.

• PDO time monitoring has responded.

• Set the correct telegram length for the CAN master

(sender).

• Eliminate disturbances in the environment (e.g. EMC).

• Select a different monitoring time or switch off time

monitoring.

Response (Lenze setting printed in bold)

Setting:

C00591/2

( Adjustable response)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

CAN on board: CAN-IN 2 error

• Incorrect PDO telegram length.

• Transmission error.

• PDO time monitoring has responded.

• Set the correct telegram length for the CAN master

(sender).

• Eliminate disturbances in the environment (e.g. EMC).

• Select a different monitoring time or switch off time

monitoring.