9400 regenerative power supply module | Parameter setting
Parameter reference
Parameter list | C00372
304
L
EDS94ARNExxxx EN 2.3 - 06/2014
C00372
Parameter | Name:
C00372 | CAN SDO server Rx identifier
Data type: BITFIELD_32
Index: 24203
d
= 5E8B
h
Identifier which serves to access the assigned SDO server.
• If bit 31 is set (0x8nnnnnnn), the corresponding SDO server is deactivated.
(see DS301 V4.02).
Value is bit-coded:
Information
Bit 0 COB-ID bit 0
• Bit 0 ... 10: COB-ID
• Bit 11 ... 30: Reserved
• Bit 31: SDO invalid
... ...
Bit 31 SDO invalid
Subcodes
Lenze setting
Information
C00372/1
0x00000601
SDO server channel 1 RX
• Subcode 1 contains the basic SDO channel which can
neither be changed nor deactivated, according to
DS301 V4.02. Writing to this subcode is ineffective.
• The value under subcode 1 results from the node
C00372/2
0x80000000
SDO server channel 2 RX
C00372/3
0x80000000
SDO server channel 3 RX
C00372/4
0x80000000
SDO server channel 4 RX
C00372/5
0x80000000
SDO server channel 5 RX
C00372/6
0x80000000
SDO server channel 6 RX
C00372/7
0x80000000
SDO server channel 7 RX
C00372/8
0x80000000
SDO server channel 8 RX
C00372/9
0x80000000
SDO server channel 9 RX
C00372/10
0x80000000
SDO server channel 10 RX
Read access Write access CINH PLC STOP No transfer