3 device diagnostics via keypad/bus system, Device diagnostics via keypad/bus system – Lenze E94ARNE Regenerative power supply User Manual

Page 190

background image

9400 regenerative power supply module | Parameter setting

Diagnostics & fault analysis

Device diagnostics via keypad/bus system

190

L

EDS94ARNExxxx EN 2.3 - 06/2014

8.3

Device diagnostics via keypad/bus system

Keypad display of the device state

Display parameters
Via the parameters listed in the following table, current states and actual values of the

regenerative power supply module can be queried for diagnostic purposes, e.g. by using

the keypad, a bus system, or the »Engineer« (when an online connection to the

regenerative power supply module has been established).

For a detailed parameter description, please see the chapter "

Parameter reference

".

( 265)

When the keypad at the front of the regenerative power

supply module is connected to the diagnostic interface

X6, the state of the regenerative power supply module

is displayed via different icons on the LCD display in the

area .

Icon

Meaning

Note

Device is ready for operation.

Device is enabled.

Application in the device is stopped.

Device is inhibited.

The power outputs are inhibited.

Device is ready to switch on.

Set current limit has been exceeded in motor

or generator mode.

Pulse inhibit is active

The power outputs are inhibited.

System fault is active

Fault is active

Trouble is active

Warning is active

Parameter

Information

Lenze setting

Value Unit

C00050

Output power (DC current)

- kW

C00051

Actual frequency

- Hz

C00052

Mains voltage

- V

C00053

DC-bus voltage

- V

C00054

Mains current

- A

C00055/1

Phase current zero system

- A

C00055/2

Phase current phase U

- A

C00055/3

Phase current phase V

- A