File projectselection.dat is invalid [0x008c0006, File projectlist.dat is invalid [0x008c0007, File devicecfg.dat is invalid [0x008c0008 – Lenze E94ARNE Regenerative power supply User Manual
Page 237: Project not loaded [0x008c0009, Project not available [0x008c000a, Required licence missing [0x008c000b, 0x008c0008, 0x008c0007, 0x008c0006, 0x008c000a

EDS94ARNExxxx EN 2.3 - 06/2014
L
237
9400 regenerative power supply module | Parameter setting
Diagnostics & fault analysis
Error messages
File ProjectSelection.dat is invalid [0x008c0006]
File ProjectList.dat is invalid [0x008c0007]
File DeviceCFG.dat is invalid [0x008c0008]
Project not loaded [0x008c0009]
Project not available [0x008c000a]
Required licence missing [0x008c000b]
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
Internal error
Reformat memory module (
project download.
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
Internal error
Reformat memory module (
project download.
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
Internal error
Reformat memory module (
project download.
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
Application could not be loaded because of a file error.
Load new or different application.
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
Application not available.
• Download application with the Engineer
• Switch off regenerative power supply module and use
another memory module with an application.
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
Memory module could not be initialised.
Two possibilities:
• Use the Engineer to download and activate an
application suitable for the memory module.
• Switch off regenerative power supply module and
insert another memory module that is suitable for the
application.