Memory module has been removed [0x00680006, Safety module has been removed [0x00680007, Control card is defect [0x00680008 – Lenze E94ARNE Regenerative power supply User Manual
Page 211: Power section is defect [0x00680009, Mxi1: module is defect or missing [0x0068000a, Mxi2: module is defect or missing [0x0068000b, 0x00680008, 0x00680006, 0x0068000a, 0x0068000b

EDS94ARNExxxx EN 2.3 - 06/2014
L
211
9400 regenerative power supply module | Parameter setting
Diagnostics & fault analysis
Error messages
Memory module has been removed [0x00680006]
Safety module has been removed [0x00680007]
Control card is defect [0x00680008]
Power section is defect [0x00680009]
MXI1: Module is defect or missing [0x0068000a]
MXI2: Module is defect or missing [0x0068000b]
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
You have tried to remove or change the memory module
during operation.
Switch off regenerative power supply module, insert
memory module, and switch on regenerative power
supply module again.
• If the error occurs again, the memory module is
defective and must be replaced.
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
You have tried to remove or change the safety module
during operation.
Switch off regenerative power supply module, insert
safety module, and switch on regenerative power supply
module again.
• If the error occurs again, the safety module is
defective and must be replaced.
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
Operating system could not identify the control card.
Please contact Lenze.
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
Operating system could not identify the power section. Please contact Lenze.
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
Operating system could not identify extension module in
module slot MXI1.
• Use a different extension module.
• Please contact Lenze.
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
Operating system could not identify extension module in
module slot MXI2.
• Use a different extension module.
• Please contact Lenze.