9 internal interfaces, 1 ls_analoginput - analog inputs, Internal interfaces – Lenze E94ARNE Regenerative power supply User Manual
Page 255: Ls_analoginput - analog inputs, 9internal interfaces

EDS94ARNExxxx EN 2.3 - 06/2014
L
255
9400 regenerative power supply module | Parameter setting
Internal interfaces
LS_AnalogInput - analog inputs
9
Internal interfaces
This chapter gives information about the system blocks of the regenerative power supply
module. The system blocks are fixedly integrated in the runtime system and provide the
application in the »Engineer« function block editor with the internal interfaces for the I/Os
and for the device and line interface.
9.1
LS_AnalogInput - analog inputs
The LS_AnalogInput system block represents the analog inputs in the function block
editor.
Output
Data type
Value/meaning
AIN1_dnIn_n
DINT
Analog input 1
• Scaling:
±2
30
≡ ±10 V for use as voltage input
±2
30
≡ ±20 mA for use as current input
AIN2_dnIn_n
DINT
Analog input 2
• Scaling: ±2
30
≡ ±10 V
AIN1_bCurrentError
BOOL
Status signal "Current input error"
• Only when analog input 1 is used as current input.
• Application: Cable-breakage monitoring of the 4 ...20 mA circuit.
TRUE |I
AIN1
| < 2 mA
A1+
A1-
A1-
A1R
A2+
A2-
AIN1_dnIn_n
AIN1_bCurrentError
AIN2_dnIn_n
X3
LS_AnalogInput
250
C02731/1 C02730/1 C02732/1
C02731/2 C02730/2 C02732/2
C02800/1
C02800/2