C00604 | resp. to device overload > c00123, C00610 | resp. to failure heatsink fan, C00611 | resp. to failure integral fan – Lenze E94ARNE Regenerative power supply User Manual
Page 319: C00612 | resp. to can node guarding error, C00604, Occu, C00612/1, Go to, C00610, C00611
EDS94ARNExxxx EN 2.3 - 06/2014
L
319
9400 regenerative power supply module | Parameter setting
Parameter reference
Parameter list | C00604
C00604
C00610
C00611
C00612
Parameter | Name:
C00604 | Resp. to device overload > C00123
Data type: UNSIGNED_32
Index: 23971
d
= 5DA3
h
Response if adjustable "I x t" warning threshold (
) is reached.
Selection list
(Lenze setting printed in bold)
1 Fault
5 Warning
0 No response
Read access Write access CINH PLC STOP No transfer
Parameter | Name:
C00610 | Resp. to failure heatsink fan
Data type: UNSIGNED_32
Index: 23965
d
= 5D9D
h
Response if fan speed of heatsink fan is too low.
Selection list
(Lenze setting printed in bold)
1 Fault
5 Warning
0 No response
Read access Write access CINH PLC STOP No transfer
Parameter | Name:
C00611 | Resp. to failure integral fan
Data type: UNSIGNED_32
Index: 23964
d
= 5D9C
h
Response if fan speed of interior fan is too low.
Selection list
(Lenze setting printed in bold)
1 Fault
5 Warning
0 No response
Read access Write access CINH PLC STOP No transfer
Parameter | Name:
C00612 | Resp. to CAN node guarding error
Data type: UNSIGNED_8
Index: 23963
d
= 5D9B
h
Response of master if the corresponding node guarding response is not received.
"CAN on board" system bus: node guarding protocol
Selection list
(Lenze setting printed in bold)
1 Fault
2 Trouble
4 Warning locked
5 Warning
6 Information
0 No response
Subcodes
Lenze setting
Information
C00612/1
0: No response
Response to non-received telegram for monitoring entry
1 ... 32
C00612/...
C00612/32
Read access Write access CINH PLC STOP No transfer