Mains voltage 10% too high [0x007b0045, Mains voltage 15% too high [0x007b0046, Filter: relay malfunction [0x007b0048 – Lenze E94ARNE Regenerative power supply User Manual
Page 230: Mains not connected [0x007b0049, 0x007b0049, 0x007b0045, 0x007b0046, 0x007c0000, 0x007c0001, 0x007b0048

9400 regenerative power supply module | Parameter setting
Diagnostics & fault analysis
Error messages
230
L
EDS94ARNExxxx EN 2.3 - 06/2014
Mains voltage 10% too high [0x007b0045]
Mains voltage 15% too high [0x007b0046]
Filter: Relay malfunction [0x007b0048]
Mains not connected [0x007b0049]
Memory module: File system has been formatted [0x007c0000]
Memory module: File system has been restored [0x007c0001]
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
Mains voltage too high.
Check mains voltage.
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
Mains voltage too high.
Check mains voltage.
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
There was no feedback from the relay in the filter, which
switches the inverter to the mains after a successful
charging process. Either the relay has not picked up, or
the feedback cable is defective.
• Check 24 V voltage supply of the filter.
• Check connecting cable between the filter and the
device (encoder plug).
• If the two previously mentioned items are OK, an
internal error has occurred within the filter (repair
required).
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
No mains connection.
Check mains connection.
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
File system of the memory module has been formatted. - (Information only)
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
File system of the memory module has been restored.