C01902 | diagnostics x6: max. baud rate, C01903 | diagnostics x6: change baud rate, C01905 | diagnostics x6: curr. baud rate – Lenze E94ARNE Regenerative power supply User Manual
Page 331: C02104 | program auto-start, C02108 | program status, C02104, Determines whether the application is, The current program state is displayed in, C02108

EDS94ARNExxxx EN 2.3 - 06/2014
L
331
9400 regenerative power supply module | Parameter setting
Parameter reference
Parameter list | C01902
C01902
C01903
C01905
C02104
C02108
Parameter | Name:
C01902 | Diagnostics X6: Max. baud rate
Data type: UNSIGNED_32
Index: 22673
d
= 5891
h
Maximum permissible baud rate of the standard device after determination of the baud rate at the diagnostics
interface X6
• Communication starts with the default baud rate (19200) of the standard device.
Selection list
(Lenze setting printed in bold)
9600 9600 baud
19200 19.200 baud
38400 38.400 baud
57600 57.600 baud
115200 115.200 baud
230400 230.400 baud
375000 375.000 baud
750000 750.000 baud
1500000 1.500.000 baud
3000000 3.000.000 baud
Read access Write access CINH PLC STOP No transfer
Parameter | Name:
C01903 | Diagnostics X6: Change baud rate
Data type: UNSIGNED_32
Index: 22672
d
= 5890
h
New determination of the baud rate at the diagnostics interface X6
Selection list
(Lenze setting printed in bold)
1 Set a higher baud rate
0 Ignore changes
Read access Write access CINH PLC STOP No transfer
Parameter | Name:
C01905 | Diagnostics X6: Curr. baud rate
Data type: UNSIGNED_32
Index: 22670
d
= 588E
h
Current baud rate at diagnostics interface X6
Display range
(min. value | unit | max. value)
0
3000000
Read access Write access CINH PLC STOP No transfer
Parameter | Name:
C02104 | Program auto-start
Data type: UNSIGNED_32
Index: 22471
d
= 57C7
h
Selection list
(Lenze setting printed in bold)
0 OFF
1 Autom. after mains connection
Read access Write access CINH PLC STOP No transfer
Parameter | Name:
C02108 | Program status
Data type: UNSIGNED_8
Index: 22467
d
= 57C3
h
Selection list
(display only)
1 Program stopped
0 Program is running
2 Program stopped at breakpoint
Read access Write access CINH PLC STOP No transfer