C00591 | resp. to can-rpdox error, C00594 | resp. to failure t. sensor filter, C00595 | resp. to can bus off – Lenze E94ARNE Regenerative power supply User Manual
Page 317: C00591/1, C00591/2, C00591/3, C00591/4, C00595, C00594

EDS94ARNExxxx EN 2.3 - 06/2014
L
317
9400 regenerative power supply module | Parameter setting
Parameter reference
Parameter list | C00591
C00591
C00594
C00595
Parameter | Name:
C00591 | Resp. to CAN-RPDOx error
Data type: UNSIGNED_8
Index: 23984
d
= 5DB0
h
Response if the corresponding CAN RPDO has not been received within the configured time or with the configured
sync.
Selection list
(Lenze setting printed in bold)
1 Fault
2 Trouble
4 Warning locked
5 Warning
6 Information
0 No response
Subcodes
Lenze setting
Information
C00591/1
0: No response
Response to non-received RPDO1 ... RPDO4
C00591/...
C00591/4
Read access Write access CINH PLC STOP No transfer
Parameter | Name:
C00594 | Resp. to failure t. sensor filter
Data type: UNSIGNED_32
Index: 23981
d
= 5DAD
h
Response to filter temperature sensor error.
• The response to a too high filter temperature via PTC input T1/T2 can be selected in
.
Selection list
(Lenze setting printed in bold)
1 Fault
5 Warning
0 No response
Read access Write access CINH PLC STOP No transfer
Parameter | Name:
C00595 | Resp. to CAN bus OFF
Data type: UNSIGNED_8
Index: 23980
d
= 5DAC
h
Response if CAN node switches to the bus off state.
Selection list
(Lenze setting printed in bold)
1 Fault
2 Trouble
4 Warning locked
5 Warning
6 Information
0 No response
Read access Write access CINH PLC STOP No transfer