I-1401/1, I-1402/1 – Lenze E94ARNE Regenerative power supply User Manual
Page 162

9400 regenerative power supply module | Parameter setting
"CAN on board" system bus
Implemented CANopen objects
162
L
EDS94ARNExxxx EN 2.3 - 06/2014
I-1401
Communication parameter for the reception of process data via RPDO2
For the assignment of the data telegram see object
.
I-1402
Communication parameter for the reception of process data via RPDO3
For the assignment of the data telegram see object
.
Index:
I-1401
Name:
RPDO2 communication parameter
Subindex
Default setting
Setting range (min. value | unit | max. value)
Access
Data type
0: Highest subindex supported
5
- (read access only)
ro
U8
1: COB-ID used by RPDO
0x300 + node ID
0
4294967295 rw
U32
2: Transmission type
254
0
255 rw
U8
3: Inhibit time
-
- (not used for RPDOs)
rw
U16
4: Compatibility entry
-
- (reserved, read or write access results in the error
message 0x06090011)
rw
U8
5: Event timer
-
- (not used for RPDOs)
rw
U16
Subindex
Meaning
Lenze code
1
Identifier RPDO2
• The basic setting corresponds to the "Predefined
Connection Set": identifier = 0x300 + node ID
2
RPDO transmission type according to DS301 V4.02
Index:
I-1402
Name:
RPDO3 communication parameter
Subindex
Default setting
Setting range (min. value | unit | max. value)
Access
Data type
0: Highest subindex supported
5
- (read access only)
ro
U8
1: COB-ID used by RPDO
0x400 + node ID
0
4294967295 rw
U32
2: Transmission type
254
0
255 rw
U8
3: Inhibit time
-
- (not used for RPDOs)
rw
U16
4: Compatibility entry
-
- (reserved, read or write access results in the error
message 0x06090011)
rw
U8
5: Event timer
-
- (not used for RPDOs)
rw
U16
Subindex
Meaning
Lenze code
1
Identifier RPDO3
• The basic setting corresponds to the "Predefined
Connection Set": identifier = 0x400 + node ID
2
RPDO transmission type according to DS301 V4.02