0x00a10008, 0x00a10005, 0x00a10006 – Lenze E94ARNE Regenerative power supply User Manual
Page 248: 0x00a10007, Diagnostics & fault analysis error messages
9400 regenerative power supply module | Parameter setting
Diagnostics & fault analysis
Error messages
248
L
EDS94ARNExxxx EN 2.3 - 06/2014
CAN module (MXI1) RPDO6: Telegram not received or faulty [0x00a10005]
CAN module (MXI1) RPDO7: Telegram not received or faulty [0x00a10006]
CAN module (MXI1) RPDO8: Telegram not received or faulty [0x00a10007]
CAN module (MXI1) PDO manager: Faulty configuration [0x00a10008]
Response (Lenze setting printed in bold)
Setting:
C13591/6
( Adjustable response)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
CANopen communication module in MXI1: CAN-IN 6
error
• Incorrect PDO telegram length.
• Transmission error.
• PDO time monitoring has responded.
• Set the correct telegram length for the CAN master
(sender).
• Eliminate disturbances in the environment (e.g. EMC).
• Select a different monitoring time or switch off time
monitoring.
Response (Lenze setting printed in bold)
Setting:
C13591/7
( Adjustable response)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
CANopen communication module in MXI1: CAN-IN 7
error
• Incorrect PDO telegram length.
• Transmission error.
• PDO time monitoring has responded.
• Set the correct telegram length for the CAN master
(sender).
• Eliminate disturbances in the environment (e.g. EMC).
• Select a different monitoring time or switch off time
monitoring.
Response (Lenze setting printed in bold)
Setting:
C13591/8
( Adjustable response)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
CANopen communication module in MXI1: CAN-IN 8
error
• Incorrect PDO telegram length.
• Transmission error.
• PDO time monitoring has responded.
• Set the correct telegram length for the CAN master
(sender).
• Eliminate disturbances in the environment (e.g. EMC).
• Select a different monitoring time or switch off time
monitoring.
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
CANopen communication module in MXI1: CAN-PDO
configuration error
• Faulty project download.
• Invalid CAN settings according to DS301V402 in the
Engineer or PLC Designer.
• Mapping variables have incorrect CANopen indexes
according to DS405.
• Repeat download.
• Correct CAN settings in the project and regenerate
project.