Safety module has been changed [0x00680018, Combination mxi1/mxi2 not possible [0x00680019, Firmware has been changed [0x0068001a – Lenze E94ARNE Regenerative power supply User Manual
Page 214: Memory module: faulty file system [0x0068001c, Firmware incompatible to control card [0x0068001e, 0x0068001f, 0x00680019, 0x0068001a, 0x0068001e, 0x0068001c

9400 regenerative power supply module | Parameter setting
Diagnostics & fault analysis
Error messages
214
L
EDS94ARNExxxx EN 2.3 - 06/2014
Safety module has been changed [0x00680018]
Combination MXI1/MXI2 not possible [0x00680019]
Firmware has been changed [0x0068001a]
Memory module: Faulty file system [0x0068001c]
Firmware incompatible to control card [0x0068001e]
Combination memory module/device not possible [0x0068001f]
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
The safety module has been changed since the last
mains switching.
- (Only information or warning locked if the hardware
type has changed as well.)
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
The combination of the extension modules plugged into
the module slots MXI1 & MXI2 is not supported.
Use a permitted module combination.
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
The firmware of the operating system has been updated. - (Information only)
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
Memory module is plugged in incorrectly or is defective. • Plug in the memory module correctly.
• Exchange defective memory module.
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
Firmware is not compatible with the hardware.
Transfer the compatible firmware.
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
The memory module used is not supported by the
regenerative power supply module according to the
licence model.
Plug in supported memory module and switch the
mains.
• The regenerative power supply module only supports
the MM220 memory module (licence: Motion Control
HighLevel).