C00388 | can node guarding status, C00390 | can error register (ds301v402), C00391 | can emergency object – Lenze E94ARNE Regenerative power supply User Manual
Page 309: C00390, C00388/1, C00391, C00392

EDS94ARNExxxx EN 2.3 - 06/2014
L
309
9400 regenerative power supply module | Parameter setting
Parameter reference
Parameter list | C00388
C00388
C00390
C00391
Parameter | Name:
C00388 | CAN node guarding status
Data type: UNSIGNED_8
Index: 24187
d
= 5E7B
h
"CAN on board" system bus: node guarding protocol
Selection list
(display only)
0 Unknown
4 Stopped
5 Operational
127 Pre-operational
Subcodes
Information
C00388/1
State of node 1 ... 32
C00388/...
C00388/32
Read access Write access CINH PLC STOP No transfer
Parameter | Name:
C00390 | CAN Error Register (DS301V402)
Data type: BITFIELD_8
Index: 24185
d
= 5E79
h
Mapping of the CANopen object
(see DS301 V4.02)
Value is bit-coded:
Information
Bit 0 Generic error
Currently only bit 0 and bit 4 contain the corresponding
information.
Bit 1 Current error (not used)
Bit 2 Voltage error (not used)
Bit 3 Temperature error (not used)
Bit 4 Communication error
Bit 5 Dev. prof. spec. err (not used)
Bit 6 Reserved
Bit 7 Manuf. spec. error (not used)
Read access Write access CINH PLC STOP No transfer
Parameter | Name:
C00391 | CAN Emergency Object
Data type: BITFIELD_32
Index: 24184
d
= 5E78
h
Identifier of the emergency telegram
• If bit 31 of this code (0x8nnnnnnn) is set, the generation of emergency telegrams is deactivated.
• Mapping of the CANopen object
(see DS301 V4.02).
Value is bit-coded:
Information
Bit 0 COB-ID bit 0
• Bit 0 ... 10: COB-ID
• Bit 11 ... 30: Reserved
• Bit 31: Emergency stop
... ...
Bit 31 Emergency inactive/active
Read access Write access CINH PLC STOP No transfer