Lenze E94ARNE Regenerative power supply User Manual
Page 18
9400 regenerative power supply module | Parameter setting
Commissioning
Short setup
18
L
EDS94ARNExxxx EN 2.3 - 06/2014
12. Confirm the note that the project has been built successfully with OK.
If no communication path has been configured for the regenerative power supply
module yet, the Communication path dialog box is displayed:
13. Set the bus connection (e. g. "Diagnostic adapter") to the regenerative power
supply module in the Communication path dialog box.
14. Click Connect to establish the online connection to the regenerative power supply
module.
• After the connection has been established successfully, the Transfer to device
dialog box is displayed.
Note: The following parameters are set automatically in the regenerative power
supply module via the electronic filter nameplate (ENP):
,
and
• »Engineer« versions ≥ V2.9 do not overwrite these parameters during a
parameter download.
• If an older »Engineer« version is used, these parameters have to be saved prior
to a parameter download and then reset manually to the saved values.
15. Click Start in the Transfer to device dialog box.
16. Confirm the query on whether the device is to be inhibited and the application is
to be stopped with Yes.
• Then the transmission is started.
17. After the transmission has been carried out successfully, confirm the query on
whether the application is to be started with Yes.
18. Also confirm the query on whether the device is to be enabled with Yes.
19. Switch on mains voltage the DC bus is charged.
20. Deactivate controller inhibit via controller enable terminal (RFR) regenerative
feedback is enabled.
21.
Controlling the regenerative power supply module via terminals