C00375 | can sdo client rx identifier, C00376 | can sdo client tx identifier, C00377 | can sdo server node address – Lenze E94ARNE Regenerative power supply User Manual
Page 306
9400 regenerative power supply module | Parameter setting
Parameter reference
Parameter list | C00375
306
L
EDS94ARNExxxx EN 2.3 - 06/2014
C00375
C00376
C00377
Parameter | Name:
C00375 | CAN SDO client Rx identifier
Data type: BITFIELD_32
Index: 24200
d
= 5E88
h
Identifier which serves to access the assigned SDO client.
• If bit 31 (0x8nnnnnnn) is set, the corresponding SDO client channel is deactivated (see DS301 V4.02).
• The client channels need not be parameterised immediately. Their functionality will only be required when using
the gateway services.
Value is bit-coded:
Information
Bit 0 COB-ID bit 0
• Bit 0 ... 10: COB-ID
• Bit 11 ... 30: Reserved
• Bit 31: SDO invalid
... ...
Bit 31 SDO invalid
Subcodes
Lenze setting
Information
C00375/1
0x80000000
SDO client channel 1 RX ... 10 RX
C00375/...
C00375/10
Read access Write access CINH PLC STOP No transfer
Parameter | Name:
C00376 | CAN SDO client Tx identifier
Data type: BITFIELD_32
Index: 24199
d
= 5E87
h
Identifier with which the assigned SDO client is able to transmit.
• If bit 31 (0x8nnnnnnn) is set, the corresponding SDO client channel is deactivated (see DS301 V4.02).
• The client channels need not be parameterised immediately. Their functionality will only be required when using
the gateway services.
Value is bit-coded:
Information
Bit 0 COB-ID bit 0
• Bit 0 ... 10: COB-ID
• Bit 11 ... 30: Reserved
• Bit 31: SDO invalid
... ...
Bit 31 SDO invalid
Subcodes
Lenze setting
Information
C00376/1
0x80000000
SDO client channel 1 TX ... 10 TX
C00376/...
C00376/10
Read access Write access CINH PLC STOP No transfer
Parameter | Name:
C00377 | CAN SDO server node address
Data type: UNSIGNED_8
Index: 24198
d
= 5E86
h
Node address of the server with which this client communicates via the selected client channel.
• The client functionality need not be activated.
• Activation of the CAN SDO client channel requires an entry (see DS301 V4.02).
Setting range
(min. value | unit | max. value)
1
127
Subcodes
Lenze setting
Information
C00377/1
1
Remote server node address for SDO client channel 1 ...
10
C00377/...
C00377/10
Read access Write access CINH PLC STOP No transfer