beautypg.com

C00375 | can sdo client rx identifier, C00376 | can sdo client tx identifier, C00377 | can sdo server node address – Lenze E94ARNE Regenerative power supply User Manual

Page 306

background image

9400 regenerative power supply module | Parameter setting

Parameter reference

Parameter list | C00375

306

L

EDS94ARNExxxx EN 2.3 - 06/2014

C00375

C00376

C00377

Parameter | Name:

C00375 | CAN SDO client Rx identifier

Data type: BITFIELD_32

Index: 24200

d

= 5E88

h

Identifier which serves to access the assigned SDO client.

• If bit 31 (0x8nnnnnnn) is set, the corresponding SDO client channel is deactivated (see DS301 V4.02).

• The client channels need not be parameterised immediately. Their functionality will only be required when using

the gateway services.

"CAN on board" system bus

Value is bit-coded:

Information

Bit 0 COB-ID bit 0

• Bit 0 ... 10: COB-ID

• Bit 11 ... 30: Reserved

• Bit 31: SDO invalid

... ...

Bit 31 SDO invalid

Subcodes

Lenze setting

Information

C00375/1

0x80000000

SDO client channel 1 RX ... 10 RX

C00375/...
C00375/10

Read access  Write access  CINH  PLC STOP  No transfer

Parameter | Name:

C00376 | CAN SDO client Tx identifier

Data type: BITFIELD_32

Index: 24199

d

= 5E87

h

Identifier with which the assigned SDO client is able to transmit.

• If bit 31 (0x8nnnnnnn) is set, the corresponding SDO client channel is deactivated (see DS301 V4.02).

• The client channels need not be parameterised immediately. Their functionality will only be required when using

the gateway services.

"CAN on board" system bus

Value is bit-coded:

Information

Bit 0 COB-ID bit 0

• Bit 0 ... 10: COB-ID

• Bit 11 ... 30: Reserved

• Bit 31: SDO invalid

... ...

Bit 31 SDO invalid

Subcodes

Lenze setting

Information

C00376/1

0x80000000

SDO client channel 1 TX ... 10 TX

C00376/...
C00376/10

Read access  Write access  CINH  PLC STOP  No transfer

Parameter | Name:

C00377 | CAN SDO server node address

Data type: UNSIGNED_8

Index: 24198

d

= 5E86

h

Node address of the server with which this client communicates via the selected client channel.

• The client functionality need not be activated.

• Activation of the CAN SDO client channel requires an entry (see DS301 V4.02).

"CAN on board" system bus

Setting range

(min. value | unit | max. value)

1

127

Subcodes

Lenze setting

Information

C00377/1

1

Remote server node address for SDO client channel 1 ...

10

C00377/...
C00377/10

Read access  Write access  CINH  PLC STOP  No transfer