C00320 | can tpdox identifier, C00321 | can rpdox identifier, C00321/1 – Lenze E94ARNE Regenerative power supply User Manual
Page 295: C00320/1, C00321/2, C00320/2, C00321/3, C00320/3, C00321/4, C00320/4

EDS94ARNExxxx EN 2.3 - 06/2014
L
295
9400 regenerative power supply module | Parameter setting
Parameter reference
Parameter list | C00320
C00320
C00321
Parameter | Name:
C00320 | CAN TPDOx identifier
Data type: BITFIELD_32
Index: 24255
d
= 5EBF
h
Identifier for TPDO1 ... TPDO4
• If bit 31 is set (0x8nnnnnnn), the TPDO is deactivated.
• The basic setting is according to the "Predefined Connection Set".
(see DS301 V4.02).
Value is bit-coded:
Information
Bit 0 COB-ID bit 0
• Bit 0 ... 10: COB-ID
• Bit 11 ... 30: Reserved
• Bit 31: PDO invalid
... ...
Bit 31 PDO invalid
Subcodes
Lenze setting
Information
C00320/1
0x00000181
Identifier TPDO1
• After a node address change and CAN reset node, the
value 0x180 + node address will be set by default.
C00320/2
0x00000281
Identifier TPDO2
• After a node address change and CAN reset node, the
value 0x280 + node address will be set by default.
C00320/3
0x00000381
Identifier TPDO3
• After a node address change and CAN reset node, the
value 0x380 + node address will be set by default.
C00320/4
0x00000481
Identifier TPDO4
• After a node address change and CAN reset node, the
value 0x480 + node address will be set by default.
Read access Write access CINH PLC STOP No transfer
Parameter | Name:
C00321 | CAN RPDOx identifier
Data type: BITFIELD_32
Index: 24254
d
= 5EBE
h
Identifier for RPDO1 ... RPDO4
• If bit 31 is set (0x8nnnnnnn), the RPDO is deactivated.
• The basic setting is according to the "Predefined Connection Set".
(see DS301 V4.02).
Value is bit-coded:
Information
Bit 0 COB-ID bit 0
• Bit 0 ... 10: COB-ID
• Bit 11 ... 30: Reserved
• Bit 31: PDO invalid
... ...
Bit 31 PDO invalid
Subcodes
Lenze setting
Information
C00321/1
0x00000201
Identifier RPDO1
• After a node address change and CAN reset node, the
value 0x200 + node address will be set by default.
C00321/2
0x00000301
Identifier RPDO2
• After a node address change and CAN reset node, the
value 0x300 + node address will be set by default.
C00321/3
0x00000401
Identifier RPDO3
• After a node address change and CAN reset node, the
value 0x400 + node address will be set by default.
C00321/4
0x00000501
Identifier RPDO4
• After a node address change and CAN reset node, the
value 0x500 + node address will be set by default.
Read access Write access CINH PLC STOP No transfer