C00598 | resp. to open circuit ain1, C00600 | resp. to dc bus overvoltage, C00601 | resp. to 10% undervoltage on line – Lenze E94ARNE Regenerative power supply User Manual
Page 318: C00602 | resp. to 10% overvoltage on line, C00600, C00598
9400 regenerative power supply module | Parameter setting
Parameter reference
Parameter list | C00598
318
L
EDS94ARNExxxx EN 2.3 - 06/2014
C00598
C00600
C00601
C00602
Parameter | Name:
C00598 | Resp. to open circuit AIN1
Data type: UNSIGNED_32
Index: 23977
d
= 5DA9
h
Response if AIN1 is parameterised to master current and LifeZero mode (±4...±20 mA) is selected and the current is
in the non-permitted range (-4...+4 mA).
Selection list
(Lenze setting printed in bold)
1 Fault
2 Trouble
4 Warning locked
5 Warning
6 Information
0 No response
Read access Write access CINH PLC STOP No transfer
Parameter | Name:
C00600 | Resp. to DC bus overvoltage
Data type: UNSIGNED_32
Index: 23975
d
= 5DA7
h
Response to DC bus overvoltage
Parameterising the brake chopper/brake resistor
Selection list
(Lenze setting printed in bold)
1 Fault
2 Trouble
Read access Write access CINH PLC STOP No transfer
Parameter | Name:
C00601 | Resp. to 10% undervoltage on Line
Data type: UNSIGNED_32
Index: 23974
d
= 5DA6
h
Mains voltage monitoring: Response to 10 % undervoltage
• Note: This parameter is only effective in closed-loop operation (in preparation).
Selection list
(Lenze setting printed in bold)
2 Trouble
5 Warning
0 No response
Read access Write access CINH PLC STOP No transfer
Parameter | Name:
C00602 | Resp. to 10% overvoltage on Line
Data type: UNSIGNED_32
Index: 23973
d
= 5DA5
h
Mains voltage monitoring: Response to 10 % overvoltage
• Note: This parameter is only effective in closed-loop operation (in preparation).
Selection list
(Lenze setting printed in bold)
2 Trouble
5 Warning
0 No response
Read access Write access CINH PLC STOP No transfer