Diagnostics & fault analysis
Error messages
Parameter set: Version conflict [0x00900007]
Parameter set: Type of standard device has been changed [0x00900009]
No parameters for module in MXI1 [0x0090000a]
No parameters for module in MXI2 [0x0090000b]
Mains voltage is switched on [0x00910000]
Mains voltage is switched off [0x00910001]
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
The parameter set version on the memory module is not
compatible with the firmware of the regenerative power
supply module.
Transfer parameter set from the Engineer to the
regenerative power supply module and save it with
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
The firmware has loaded a parameter set the type code
of which does not correspond to the type code of the
regenerative power supply module.
Load a suitable parameter set.
Response (Lenze setting printed in bold)
Setting:
( Adjustable response)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
The parameter set contains no parameters for the
module inserted in MXI1.
Integrate the module inserted in MXI1 into the Engineer
project and then transmit the parameter set to the
regenerative power supply module again.
Response (Lenze setting printed in bold)
Setting:
( Adjustable response)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
The parameter set contains no parameters for the
module inserted in MXI2.
Integrate the module inserted in MXI2 into the Engineer
project and then transmit the parameter set to the
regenerative power supply module again.
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
Mains voltage has been switched on.
- (Information only)
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
Mains voltage has been switched off.
- (Information only)