EDS94ARNExxxx EN 2.3 - 06/2014

L

81

9400 regenerative power supply module | Parameter setting

Device interface

Device states

4.2.2

State "Device is ready to switch on"

This is the device state of the regenerative power supply module directly after the

initialisation has been completed and a DC-bus voltage is not applied yet.

The bus systems are running and the terminals and encoders are evaluated.

The monitoring functions are active.

The regenerative power supply module can be parameterised and device commands

can be executed to a limited extent.

The application is basically executable.

4.2.3

State "Device is switched on"

This is device state of the regenerative power supply module when the DC-bus voltage is

applied and the regenerative power supply module is still inhibited by the user (controller

inhibit).

The bus systems are running and the terminals and encoders are evaluated.

The monitoring functions are active.

The regenerative power supply module can be parameterised and device commands

can be executed to a limited extent.

The application is basically executable.

LED DRIVE READY

LED DRIVE ERROR

Display in

C00183

OFF

141: Device ready to start

Note!

The "Device is ready to switch on" state is not only entered after power-on, but

also when a "Trouble" or "Fault" is reset.
• For

C00142

= "1: Enabled", the device changes directly from the "Device is

ready to switch on" state to the "Device is switched on" state (Lenze setting).

• For

C00142

= "0: Inhibited", at least one source for controller must be active

to get from the "Device is ready to switch on" state to the "Device is switched

on" state.

Automatic restart after power-on/trouble/fault

( 84)

LED DRIVE READY

LED DRIVE ERROR

Display in

C00183

OFF

90: Drive switched on