4 error id, 5 example for the bit coding of the error number, Error id – Lenze E94ARNE Regenerative power supply User Manual
Page 201: Example for the bit coding of the error number
EDS94ARNExxxx EN 2.3 - 06/2014
L
201
9400 regenerative power supply module | Parameter setting
Diagnostics & fault analysis
Error messages
8.6.1.4
Error ID
16-bit value (0 ... 65535
dec
) for error identification.
8.6.1.5
Example for the bit coding of the error number
displays the error number "1148911631".
This decimal value corresponds to the following bit sequence:
Error number "1148911631" thus means:
The "DC-bus undervoltage" error with the response "Trouble" has occurred in the
"Control" module with the instance ID 1.
0x00ad
173
CAN module in MXI2: CAN-NMT handler
0x00ae
174
CAN module in MXI2: CAN emergency handler
0x00af
175
CAN module in MXI2: CAN-NMT master
0x00b0
176
CAN module in MXI2: CAN-PDO handler
0x00b1
177
CAN module in MXI2: CAN-SDO server
0x00b2
178
CAN module in MXI2: CAN-SDO client
0x00c8
200
Intelligent communication module
Module ID
Module
hex
decimal
Bit 31
16
25
26
28
29
0
15
Assignment
Information
Meaning in the example
2: Trouble
1: Instance ID 1
Module ID 0x007b: control
Error ID 0x000f for control:
Bit 31
16
25
26
28
29
0
15
0 1 0 0 0 1 0 0 0 1 1 1 1 0 1 1 0 0 0 0 0 0 0 0 0 0 0 0 1 1 1 1
0 1 0
0 0 1
0 0 0 1 1 1 1 0 1 1
0 0 0 0 0 0 0 0 0 0 0 0 1 1 1 1