3 commissioning example, Commissioning example – Lenze E94ARNE Regenerative power supply User Manual
Page 143

EDS94ARNExxxx EN 2.3 - 06/2014
L
143
9400 regenerative power supply module | Parameter setting
"CAN on board" system bus
Monitoring
6.9.2.3
Commissioning example
Task
A 9400 controller configured as heartbeat consumer (node 2) is to monitor another 9400
controller (heartbeat producer; node 1).
The heartbeat producer is to send a heartbeat telegram to the heartbeat consumer
every 10 ms.
The heartbeat consumer monitors the arrival of the heartbeat telegram. If an error
occurs, a response is to be initiated.
Parameterising the heartbeat producer (node 1)
1. Set the heartbeat producer time (
) to 10 ms.
Parameterising the heartbeat consumer (node 2)
1. Configure the heartbeat monitoring in
– Note: The heartbeat consumer time must be longer than the heartbeat producer
time set for the monitored node in
.
– The value to be entered in a free subcode (1 ... 32) is "0x0001000F". It consists of the
following components:
2. Go to
and set the respective responses for the monitoring functions
parameterised in
, which are to be initiated in the consumer when a
"heartbeat event" occurs.
Tip!
•
displays the activity of the monitoring functions parameterised in
in a bit-coded manner.
•
display the heartbeat states of the monitored nodes.
•
serves to set the state change for a "heartbeat event".
Heartbeat telegram
The heartbeat telegram from the producer has the following identifier:
Identifier (COB-ID) = 1792 + node address of the producer = 1792 + 1 = 1793 = 0x701
Bit 31 ... bit 24
Reserved
Bit 23 ... bit 16
Node address
of the producer
Bit 15 ... bit 0
Heartbeat consumer time
(integer multiple of 5 ms)
0x00
0x01
15 [ms] = 0x000F