Analog input 1: master current < 4 ma [0x007d0000, Plc configuration invalid [0x007d0001, 0x007d0000 – Lenze E94ARNE Regenerative power supply User Manual
Page 231: 0x007f0002, 0x007f0003, 0x007d0001, Diagnostics & fault analysis error messages
EDS94ARNExxxx EN 2.3 - 06/2014
L
231
9400 regenerative power supply module | Parameter setting
Diagnostics & fault analysis
Error messages
Analog input 1: Master current < 4 mA [0x007d0000]
PLC configuration invalid [0x007d0001]
Communication error between device and device module [0x007f0002]
Communication with module in MXI1 interrupted [0x007f0003]
Response (Lenze setting printed in bold)
Setting:
( Adjustable response)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
Master current is in the impermissible range -4 ... +4 mA,
e.g. due to a cable break or a defective master current
value encoder.
• Only for parameterisation as master current input
(see
Remove open circuit.
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
An invalid control configuration has occurred.
Load another application.
Response (Lenze setting printed in bold)
Setting:
( Adjustable response)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
Communication between regenerative power supply
module and extension module is interrupted, e.g. due to
disturbances in the environment (EMC), defective
hardware, or loose contact.
• This monitoring function is intended for safe
communication via process data.
• Eliminate EMC disturbances.
• Switch off regenerative power supply module, insert
extension module correctly, and switch on the
regenerative power supply module again.
• Mains switching, or restart of regenerative power
supply module.
• Replace extension module/regenerative power
supply module.
• Please contact Lenze if the problem occurs again.
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
It is not possible to establish communication between
the regenerative power supply module and the
extension module in the MXI1 module slot.
• Switch off regenerative power supply module, insert
extension module correctly in module slot MXI1, and
switch on the regenerative power supply module
again.
• If the problem occurs again, replace the extension
module.