9400 regenerative power supply module | Parameter setting

Diagnostics & fault analysis

Error messages

Analog input 1: Master current < 4 mA [0x007d0000]

PLC configuration invalid [0x007d0001]

Communication error between device and device module [0x007f0002]

Communication with module in MXI1 interrupted [0x007f0003]

Response (Lenze setting printed in bold)

Setting:

C00598

( Adjustable response)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

Master current is in the impermissible range -4 ... +4 mA,

e.g. due to a cable break or a defective master current

value encoder.

• Only for parameterisation as master current input

(see

C00034

).

Remove open circuit.

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

An invalid control configuration has occurred.

Load another application.

Response (Lenze setting printed in bold)

Setting:

C01501

( Adjustable response)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

Communication between regenerative power supply

module and extension module is interrupted, e.g. due to

disturbances in the environment (EMC), defective

hardware, or loose contact.

• This monitoring function is intended for safe

communication via process data.

• Eliminate EMC disturbances.

• Switch off regenerative power supply module, insert

extension module correctly, and switch on the

regenerative power supply module again.

• Mains switching, or restart of regenerative power

supply module.

• Replace extension module/regenerative power

supply module.

• Please contact Lenze if the problem occurs again.

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

It is not possible to establish communication between

the regenerative power supply module and the

extension module in the MXI1 module slot.

• Switch off regenerative power supply module, insert

extension module correctly in module slot MXI1, and

switch on the regenerative power supply module

again.

• If the problem occurs again, replace the extension

module.