2 ixt utilisation of brake transistor, Ixt utilisation of brake transistor – Lenze E94ARNE Regenerative power supply User Manual
Page 26
9400 regenerative power supply module | Parameter setting
Regenerative power supply module application
Parameterising the brake chopper/brake resistor
26
L
EDS94ARNExxxx EN 2.3 - 06/2014
3.1.3.2
Ixt utilisation of brake transistor
The regenerative power supply module monitors the Ixt utilisation of the internal brake
transistor.
[3-1]
Signal flow of Ixt utilisation - brake chopper
The monitoring function is based on a mathematical model which calculates the
braking current from the current DC-bus voltage and the brake resistance
parameterised.
– Hence, the monitoring function can respond even if no brake resistor is connected
and can therefore also be used for a testing mode to check the parameterisation.
The calculation considers the thermal utilisation of the brake transistor by a
correspondingly adapted time constant.
to select whether the minimum brake resistance depending on the mains
(display in
), or the brake resistance value parameterised in
is to be used as a reference for calculating the utilisation.
displays the calculated utilisation of the brake transistor in [%].
– A 100 % utilisation corresponds to the continuous braking power which is provided
by the brake chopper at a DC-bus voltage of 790 V (or 390 V at a mains voltage of
230 V).
– The maximum braking power (assuming that the utilisation starts at 0 %) can be
provided for a period depending on the device.
– The calculated utilisation is also provided as the oscilloscope signal
Common.dnIxtBrakeChopper to check the braking operation while the system is
running
(scaling: 2
30
≡ 100 %).
If the utilisation exceeds the advance warning threshold set in
, the message
"Brake chopper: Ixt > C00570" is entered into the logbook and the response set in
(default setting: "Warning") is activated.
Note!
The braking operation will never be switched off by this monitoring function.
Ixt
C00137
1
0
C00134
C00129
C00133
T
= 0
Off
T
= 1
On
100 %
C00570
C00569
C00573
Logbook entry "Brake chopper: Ixt > C00570"
Logbook entry "
"
Brake chopper: Ixt overload
U
DC_act
U
DC_act
I
=
Br
I
=
Br
I
Br
= f(duty cycle, R )
Br