beautypg.com

I-1801/1 – Lenze E94ARNE Regenerative power supply User Manual

Page 166

background image

9400 regenerative power supply module | Parameter setting

"CAN on board" system bus

Implemented CANopen objects

166

L

EDS94ARNExxxx EN 2.3 - 06/2014

Subindex 3 - inhibit time
The inhibit time can only be changed if the PDO is not active (subindex 1, bit 31 = 1). The

entered value multiplied by 0.1 gives the inhibit time in [ms]. The calculated inhibit time is

always rounded down to a whole value.
Example:

Entered value: 26

Calculated time = 26 * 0.1 [ms] = 2.6 [ms]  inhibit time = 2 [ms}

I-1801

Communication parameter for the transmission of process data via TPDO2

For the assignment of the data telegram see object

I-1800

.

Index:

I-1801

Name:

TPDO2 communication parameter

Subindex

Default setting

Setting range (min. value | unit | max. value)

Access

Data type

0: Highest subindex supported

5

- (read access only)

ro

U8

1: COB-ID used by TPDO

0x280 + node ID

0

4294967295 rw

U32

2: Transmission type

254

0

255 rw

U8

3: Inhibit time

0 ms

0

0.1 ms

65535 rw

U16

4: Reserved

-

- (reserved, read or write access results in the error

message 0x06090011)

rw

U8

5: Event timer

0 ms

0

ms

65535 rw

U16

Subindex

Meaning

Lenze code

1

Identifier TPDO2

• The basic setting corresponds to the "Predefined

Connection Set": identifier = 0x280 + node ID

C00320/2

2

TPDO transmission type according to DS301 V4.02

Transmission type ( 113)

C00322/2

3

Minimum time interval between the transmission of

two identical TPDOs (see DS301 V4.02).

C00324/2

5

Cycle time for the transmission of PDOs with

transmission type "254".

C00356/2