1 parameter data object identifiers, Parameter data object identifiers – Lenze E94ARNE Regenerative power supply User Manual
Page 121
EDS94ARNExxxx EN 2.3 - 06/2014
L
121
9400 regenerative power supply module | Parameter setting
"CAN on board" system bus
Parameter data transfer
6.7.1
Parameter data object identifiers
In the Lenze setting, the identifier for the parameter data objects SDO1 ... SDO10 consists
of a basic identifier and the node address set in
Identifier (COB-ID) = basic identifier + node address (node ID)
In the Lenze setting, the basic identifiers of the SDOs are preset according to the
"Predefined Connection Set" of DS301 V4.02:
Parameter data object
Direction
Basic identifier
From the device
To the device
dec
hex
SDO1
(parameter data channel 1)
1408
580
1536
600
SDO2 ... 10
(parameter data channels 2 ... 10)
Deactivated
Node guarding, heartbeat
1792
700
Boot up
1792
700
Note!
Please observe that the parameter data channels 2 ... 10 are deactivated in the
Lenze setting.
The procedure for activating these parameter data channels is explained in the
description for the parameters
and
the implemented CAN object
.