Can module (mxi2): lifeguarding error [0x00ad0020, 0x00ac0002, 0x00ad0021 – Lenze E94ARNE Regenerative power supply User Manual
Page 250: 0x00ad0000, 0x00ad0020, Diagnostics & fault analysis error messages

9400 regenerative power supply module | Parameter setting
Diagnostics & fault analysis
Error messages
250
L
EDS94ARNExxxx EN 2.3 - 06/2014
CAN module (MXI2): Basic configuration invalid [0x00ac0002]
CAN module (MXI2): Heartbeat error index 1 ... 32 [0x00ad0000 ... 0x00ad001f]
CAN module (MXI2): Lifeguarding error [0x00ad0020]
CAN module (MXI2): Faulty NMT slave configuration [0x00ad0021]
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
CANopen communication module in MXI2:
Configuration error
• Faulty download of an Engineer or PLC Designer
project
• Invalid CAN settings according to DS301V402 in the
Engineer or PLC Designer.
• Repeat download
• Correct CAN settings in the project and regenerate
project.
Response (Lenze setting printed in bold)
Setting:
C14613/1...32
( adjustable response)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
CANopen communication module in MXI2: Cyclic node
monitoring
• Node has not received a heartbeat telegram from
node 1 ... 32 within the defined time.
• Reactivate CAN node by mains switching, restart of
the regenerative power supply module,
(
="11000") or CAN reset node.
• Reparameterise the heartbeat producer monitoring
time or switch off monitoring and reset locked error
status, if necessary.
Tip: Save the current parameter set before mains
switching and restarting the regenerative power supply
module (
="11").
Response (Lenze setting printed in bold)
Setting:
C14614
( Adjustable response)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
CANopen communication module in MXI2: Cyclic node
monitoring
• Slave response: Maximum time between two node
guarding telegrams (remote transmission request
telegram) from the master has been exceeded.
Reparameterise the life guarding monitoring time or
switch off monitoring.
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
CANopen communication module in MXI2: A
configuration error has occurred in the network
management of the CAN slave.
• Faulty download of an Engineer or PLC Designer
project
• Invalid CAN settings according to DS301V402 in the
Engineer or PLC Designer.
• Incorrect parameterisation of node guarding or
heartbeat.
• Repeat download
• Correct CAN settings in the project and regenerate
project.