9400 regenerative power supply module | Parameter setting
Commissioning
Short setup
14
L
EDS94ARNExxxx EN 2.3 - 06/2014
2.1.2
Commissioning with the keypad
1. Switch on 24-V supply of the regenerative power supply module.
– With the first switch-on of the regenerative power supply module, the filter data are
automatically read out of the electronic filter nameplate (ENP) and temporarily
saved in the regenerative power supply module.
2. If the mains voltage is not 400/415 V, adapt the Lenze setting in
accordingly.
– Note: A change of the setting in
also has an impact on the permissible device
utilisation! In the chapter "Rated data" of the Hardware Manual, the device types
and their permissible device utilisation at different mains voltages and switching
frequencies are specified.
3. Carry out optional parameter setting:
–
Parameterising the brake chopper/brake resistor
–
4. Save the parameter set (
= "11: Save start parameters").
– By saving the parameter set, certain data such as the filter data are permanently
available in the regenerative power supply module and do not need to be read again
from the electronic filter nameplate at the next switch-on. This shortens the
initialisation time correspondingly.
5. Switch on mains voltage the DC bus is charged.
6. Deactivate controller inhibit via controller enable terminal (RFR) regenerative
feedback is enabled.
7.
Controlling the regenerative power supply module via terminals
.