Electronic nameplate: data loaded [0x007b0030, Electronic nameplate: not found [0x007b0031, Internal communication error (dma) [0x007b0034 – Lenze E94ARNE Regenerative power supply User Manual
Page 228: Plc configuration invalid [0x007b0037, 0x007b0030, 0x007b0032, 0x007b0033, 0x007b0031, 0x007b0034, 0x007b0036

9400 regenerative power supply module | Parameter setting
Diagnostics & fault analysis
Error messages
228
L
EDS94ARNExxxx EN 2.3 - 06/2014
Electronic nameplate: Data loaded [0x007b0030]
Electronic nameplate: Not found [0x007b0031]
Electronic nameplate: Encoder protocol unknown [0x007b0032]
Electronic nameplate: Encoder signal unknown [0x007b0033]
Internal communication error (DMA) [0x007b0034]
Internal communication error (MCTRL host) [0x007b0036]
PLC configuration invalid [0x007b0037]
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
New electronic nameplate (ENP) has been found.
- (Information only)
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
Electronic nameplate (ENP) is not available.
- (Information only)
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
The connected filter with feedback is not supported by
the device firmware.
Check device dimensioning.
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
The connected filter with feedback is not supported by
the device firmware.
Check device dimensioning.
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
Internal error.
Please contact Lenze.
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
Internal error.
Please contact Lenze.
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
An invalid control configuration has occurred.
Load another application.