2 write parameters, Write parameters – Lenze E94ARNE Regenerative power supply User Manual
Page 129
EDS94ARNExxxx EN 2.3 - 06/2014
L
129
9400 regenerative power supply module | Parameter setting
"CAN on board" system bus
Parameter data transfer
6.7.3.2
Write parameters
Task: In the controller with the node address "2", the rated current of the connected motor
is to be entered with I
rated
= 10.2 A (code C00088).
Telegram to the drive
Response telegram from the drive (for successful execution)
Identifier
User data
1st byte
2nd byte 3rd byte
4th byte
5th byte
6th byte
7th byte
8th byte
Command
Index
Subindex
Data 1
Data 2
Data 3
Data 4
0x0602
0x23
0xA7
0x5F
0x00
0x66
0x00
0x03
0x00
Explanations - telegram to drive
Identifier
= 1536 + node address = 1536 + 2 = 1538 = 0x0602
(1536 = basic identifier of SDO1 to the controller)
Command
= 0x23 = "write request" (request to write a parameter to the controller)
Index
= 24575 - code number = 24575 - 88 = 24487 = 0x5FA7
Subindex
= 0 (code C00088 has no subcodes)
Data 1 ... 4
= 10.2 x 10 = 102 = 0x00030066
(value for motor current; data type U32; display factor 1/10)
Identifier
User data
1st byte
2nd byte 3rd byte
4th byte
5th byte
6th byte
7th byte
8th byte
Command
Index
Subindex
Data 1
Data 2
Data 3
Data 4
0x0582
0x60
0xA7
0x5F
0x00
0x00
0x00
0x00
0x00
Explanations - telegram from drive
Identifier
= 1408 + node address = 1408 + 2 = 1410 = 0x0582
(1408 = basic identifier of SDO1 from the controller)
Command
= 0x60 = "write response" (acknowledgement of the write access from the controller)
Index
Same as for telegram to the drive
Subindex