9400 regenerative power supply module | Parameter setting

"CAN on board" system bus

Implemented CANopen objects

154

L

EDS94ARNExxxx EN 2.3 - 06/2014

I-1016

Monitoring time for heartbeat monitoring of nodes 1 ... 32.

Heartbeat protocol

( 140)

The parameterised time is rounded down to an integer multiple of 5 ms. Its value must

be higher than the heartbeat producer time of the node to be monitored.

[6-8]

Assignment of the data telegram

I-1017

Time interval for sending the heartbeat telegram to the consumer(s).

Heartbeat protocol

( 140)

The parameterised time interval is rounded down to an integer multiple of 5 ms.

The heartbeat telegram is sent automatically if a time interval > 0 ms is set. In this case

the "node guarding" monitoring function is deactivated.

This object is related to the Lenze code

C00381

.

Index:

I-1016

Name:

Consumer heartbeat time

Subindex

Default setting

Setting range (min. value | unit | max. value)

Access

Data type

0: Highest subindex supported

32

- (read access only)

ro

U32

1 ... 32: Consumer heartbeat time

0

0

4294967295 rw

U32

Subindex

Meaning

Lenze code

0

Number of nodes to be monitored

1 ... 32

Node ID and heartbeat time of node 1 ... 32 to be

monitored

C00385/1...32

8th byte

7th byte

6th byte

5th byte

Data 4

Data 3

Data 2

Data 1

Bit 31 ... bit 24

Bit 23 ... bit 16

Bit 15 ... bit 0

0

(reserved)

Node ID

Heartbeat time

in [ms]

Index:

I-1017

Name:

Producer heartbeat time

Subindex

Default setting

Setting range (min. value | unit | max. value)

Access

Data type

0: Producer heartbeat time

0

0

ms

65535 rw

U32