Page 154: Object
9400 regenerative power supply module | Parameter setting
"CAN on board" system bus
Implemented CANopen objects
154
L
EDS94ARNExxxx EN 2.3 - 06/2014
I-1016
Monitoring time for heartbeat monitoring of nodes 1 ... 32.
The parameterised time is rounded down to an integer multiple of 5 ms. Its value must
be higher than the heartbeat producer time of the node to be monitored.
[6-8]
Assignment of the data telegram
I-1017
Time interval for sending the heartbeat telegram to the consumer(s).
The parameterised time interval is rounded down to an integer multiple of 5 ms.
The heartbeat telegram is sent automatically if a time interval > 0 ms is set. In this case
the "node guarding" monitoring function is deactivated.
This object is related to the Lenze code
Index:
I-1016
Name:
Consumer heartbeat time
Subindex
Default setting
Setting range (min. value | unit | max. value)
Access
Data type
0: Highest subindex supported
32
- (read access only)
ro
U32
1 ... 32: Consumer heartbeat time
0
0
4294967295 rw
U32
Subindex
Meaning
Lenze code
0
Number of nodes to be monitored
1 ... 32
Node ID and heartbeat time of node 1 ... 32 to be
monitored
8th byte
7th byte
6th byte
5th byte
Data 4
Data 3
Data 2
Data 1
Bit 31 ... bit 24
Bit 23 ... bit 16
Bit 15 ... bit 0
0
(reserved)
Node ID
Heartbeat time
in [ms]
Index:
I-1017
Name:
Producer heartbeat time
Subindex
Default setting
Setting range (min. value | unit | max. value)
Access
Data type
0: Producer heartbeat time
0
0
ms
65535 rw
U32