"CAN on board" system bus
Monitoring
136
L
EDS94ARNExxxx EN 2.3 - 06/2014
6.9.1.2
Parameter setting
Short overview of parameters for the "node guarding" monitoring function:
Guard time
The "guard time" is the time interval at which the NMT master sends the RTR telegram.
For each NMT slave to be monitored an individual time interval can be set.
The RTR telegram requests the NMT slave to send its current state.
Node life time
The "node life time" is the product of the "guard time" and the "life time factor":
Node life time = guard time x life time factor
"Life time factor" and "guard time" must be known to the NMT master. For this reason,
the values are read from the NMT slave or defined values are sent to the NMT slave at
every restart.
For each NMT slave to be monitored an individual "node life time" can be set.
OK state
The connection state is OK if
the NMT slave has received an RTR telegram from the NMT master and
the NMT master has received a correct response from the requested NMT slave within
the ”node life time”.
In the OK state, the monitoring times for the NMT master and the NMT slave are reset and
the node guarding protocol is continued.
Parameter
Information
Lenze setting
Assignment
Value Unit
Master
Slave
CAN Guard Time
0 ms
CAN Life Time Factor
0
CAN Node Guarding
0x00000000
CAN Node Guarding Activity
-
CAN Node Guarding Status
-
Resp. to CAN node guarding error
No response
Resp. to CAN life guarding error
No response
CAN behaviour in case of fault
Pre-operational state
Highlighted in grey = display parameter