Yokogawa DAQWORX User Manual
Page 293

8-36
IM WX104-01E
Tme Event
Set the Time Event.
Click this tab
• On1/On2/On3/Off
Set the ON/OFF setting type of each event (16 events) from the following. Select [Off]
for events that are not to be assigned.
On1: Use On time and Off time
On2: Use On time only
On3: Use Off time only
• On-time/Off-time
Set the ON-time/OFF-time of the time event in “hh:mm:ss” format. The selectable
range is “00:00:00 to 99:59:59.” Set On-time ≤ Off-time.
Repeat
Set the repeat action.
The repeat start segment, repeat end segment, and repeat frequency is displayed in the
program display screen.
Repeat action
Repeat frequency
Repeat start segment
Click this tab
Repeat end segment
• Repeat action
Select the repeat function from [Off], [On], and [Repeat].
• Repeat frequency
Set the number of repetitions when the repeat function is turned ON in the range of [1]
to [999].
• Repeat start segment/Repeat end segment
Set the repeat start segment number and the repeat end segment number when the
repeat function is turned ON or when repeating in the range of “1 to 99.” However, the
maximum value is the maximum segment number set for the pattern. The selectable
range for the maximum value is
Set repeat start segment ≤ repeat end segment.
8.6 Program Control Related Setup Operatons